Welcome to Agasti Tank Works Pvt Ltd marketing@agasticorporation.com
Certified Company
ISO 14001 :2015
Certified Company
ISO 45001 :2018
Certified Company
ISO 9001 :2015
Call Us
+91-9579868575

Rim Seal Fire Protection System (RSFPS)

Rim Seal Fire Protection System (RSFPS)

A Rim Seal Fire Protection System (RSFPS) is an automatic fire detection and suppression system specifically designed to protect the rim seal area of External Floating Roof Tanks (EFRTs) where the majority of floating roof fires originate. The system continuously monitors the complete 360° rim seal using Distributed Fibre Optic Linear Heat Detection (LHD) technology, accurately detects abnormal temperature rise, pinpoints the fire location, and automatically actuates a foam suppression system to extinguish the fire at its source. The system is designed to provide rapid response, minimize hydrocarbon fire escalation, reduce false alarms, and enhance personnel, asset, and environmental safety. The uploaded presentation describes a fibre-optic sensing cable, explosion-proof junction boxes, a control panel, and an automatic foam discharge system integrated with plant SCADA/DCS.

Typical Application

  • External Floating Roof Tanks (EFRTs).
  • Crude Oil Storage Tanks.
  • Gasoline, Naphtha, Diesel, ATF and Kerosene Storage Tanks.
  • Refineries and Petrochemical Plants.
  • Oil Marketing Company (OMC) Terminals.
  • Tank Farms and Bulk Liquid Storage Facilities.
  • LNG/LPG auxiliary hydrocarbon storage where floating roof tanks are used.
  • New installations and retrofit projects requiring automatic rim seal fire protection.

 

Guideline / Standard

Storage Tank Standards:

  • API 650 – Welded Tanks for Oil Storage.
  • API 653 – Inspection, Repair, Alteration and Reconstruction of Storage Tanks.
  • API RP 545 Rev.1 – Lightning Protection of Aboveground Storage Tanks.
  • API 2003 – Protection Against Ignitions Arising Out of Static, Lightning and Stray Currents.
  • API 2350 – Overfill Protection for Storage Tanks.

Fire Detection Standards:

  • EN 54-22 – Resettable Line-Type Heat Detectors (Distributed Fibre Optic LHD).
  • NFPA 72 – National Fire Alarm and Signaling Code.

Foam Fire Protection Standards:

  • NFPA 11 – Standard for Low-, Medium-, and High-Expansion Foam Systems.
  • UL Listed Foam Equipment (where specified).

Hazardous Area Standards:

  • NFPA 780 – Lightning Protection Systems.
  • IEC 60079-0 – Explosive Atmospheres – General Requirements.
  • IEC 60079-28 – Protection of Equipment Using Optical Radiation.
  • ATEX / IECEx Certification for hazardous areas.
  • IEC 61508 (SIL-2) – Functional Safety (where applicable).

Indian Standards:

  • OISD-117 – Fire Protection Facilities for Petroleum Depots, Terminals and Pipeline Installations (including Appendix C for Rim Seal Foam Systems).
  • OISD-244 – Fire Protection Requirements for Petroleum Installations.
  • PESO approval requirements for foam system components and hazardous area equipment. These standards are also reflected in the presentation's approvals section.

Material of Construction (MOC)

Distributed Heat Detection Cable: Multi-mode/Single-mode Glass Fibre Optic Cable with UV-, oil-, and chemical-resistant LSZH/HDPE outer jacket.
Foam Pressure Vessel: Stainless Steel SS316, designed and fabricated in accordance with ASME Section VIII Div. 1.
Foam Concentrate: UL Listed 3% AFFF or Fluorine-Free Foam (F3) as specified by project/environmental requirements.
Pressurizing Medium: Dry Nitrogen (N₂).
Foam Piping: Carbon Steel (ASTM A106/API 5L) with epoxy coating or Stainless Steel SS304/SS316 depending on service conditions.
Foam Discharge Nozzles: UL Listed Stainless Steel SS316 or corrosion-resistant Brass Alloy.
Explosion-Proof Junction Boxes: LM6 Aluminium Alloy (Epoxy Coated) or Stainless Steel SS316, Ex-certified.
Control Panel: IP65/IP66 Powder-Coated Carbon Steel or SS304/SS316 enclosure.
Isolation Valves: SS316 Ball Valves or Carbon Steel Valves with corrosion-resistant coating.
Fasteners & Mounting Brackets: Stainless Steel SS304/SS316.
Cable Supports & Clamps: Stainless Steel SS304/SS316 with UV-resistant polymer inserts where required. The presentation specifically identifies an SS316 foam vessel built to ASME Section VIII Div. 1, nitrogen pressurization, UL-listed AFFF foam, and explosion-proof field hardware.